Three Phase Power Calculator

Enter your line voltage, current per phase and power factor, and this three phase power calculator returns real power in kW, apparent power in kVA, reactive power in kVAR — or works backwards from kW to current.

Your three-phase load
line-to-line: P = sqrt(3) x V x I x PF · line-to-neutral: P = 3 x V x I x PF · apparent S = sqrt(3) x V x I (line-to-line) · current I = P / (sqrt(3) x V x PF)

Balanced three-phase load assumed, and current is per phase (what a clamp meter reads on one conductor). Common line-to-line voltages: 208 V, 400 V, 480 V, 600 V. Use 1.0 power factor for resistive loads (heaters, lights) or the motor nameplate value.

Planning estimate only. Sizing conductors, breakers and transformers is safety-critical work — verify with nameplate data, local electrical code and a qualified electrician.

How the three phase power calculator works

Three-phase power uses the square root of 3 (1.732) because the three phases sit 120 degrees apart. With line-to-line voltage, real power is P = sqrt(3) x V x I x PF, apparent power is S = sqrt(3) x V x I, and reactive power is Q = sqrt(S squared minus P squared). With line-to-neutral voltage the multiplier is 3 instead of sqrt(3) — both forms give the same answer on a balanced load.

Worked examples: a 400 V line-to-line load at 10 A per phase with 0.85 power factor draws sqrt(3) x 400 x 10 x 0.85 = 5,889 W. A 480 V load at 50 A with 0.85 power factor draws about 35.3 kW (41.6 kVA apparent). To size a feeder instead, rearrange: I = P / (sqrt(3) x V x PF).

Common mistakes: entering total current instead of per-phase current, using line-to-neutral voltage in the line-to-line formula (or the reverse), and forgetting power factor — apparent power in kVA is always larger than real power in kW for motors, and breakers and transformers are sized on current and kVA, not kW alone.

line-to-line: P = sqrt(3) x V x I x PF · S = sqrt(3) x V x I · Q = sqrt(S^2 - P^2) · line-to-neutral: P = 3 x V x I x PF

Related tools

Convert small currents with the Milliamps to Amps Calculator, or estimate the energy side with the Solar Panel Cost Calculator.

Three phase power calculator FAQ

What is the three phase power formula?

With line-to-line voltage: P = sqrt(3) x V x I x power factor. With line-to-neutral voltage: P = 3 x V x I x power factor. Both assume a balanced load.

How do I calculate three-phase amps from kW?

Rearrange the formula: I = P / (sqrt(3) x V x PF) for line-to-line voltage. A 35.4 kW load at 480 V with 0.85 power factor draws about 50 A per phase.

What is the difference between kW, kVA and kVAR?

kW is real power that does work, kVA is apparent power the system must deliver, and kVAR is reactive power stored and returned each cycle. They relate by kVA squared = kW squared + kVAR squared.

What power factor should I use?

Use 1.0 for resistive loads like heaters and lights, and the motor or equipment nameplate value for motors — 0.85 is a common planning estimate when the nameplate is unavailable.

What is line-to-line vs line-to-neutral voltage?

Line-to-line is measured across two phase conductors (for example 400 V or 480 V); line-to-neutral is measured from one phase to neutral (400 V line-to-line is 230 V phase voltage in a wye system). Most industrial equipment is specified line-to-line.

Is the current per phase or total?

Per phase — the value a clamp meter reads on a single conductor. Do not add the three phases together; the sqrt(3) factor already accounts for all three.

Can I use this for an unbalanced load?

No. These formulas assume a balanced three-phase load. Unbalanced loads need per-phase calculations and, for sizing work, a qualified electrician.